VITALink® Armored Fire Resistive

Photo of VITALink Armored Fire Resistive

Unshielded Construction:

  • Conductors: 14 AWG Solid Bare Copper
  • Tape: Heat Resistant Tape
  • Insulation: LZSH Thermoset Fire-Roc™
  • Binder: White Fire-Roc™ Binder
  • Armor: CCW Copper
  • Optional Jacket: Non-Halogen Flame Retardant Polyolefin

Shielded Construction:

  • Conductors: 16 AWG Solid Bare Copper
  • Tape: Heat Resistant Tape
  • Insulation: LZSH Thermoset Fire-Roc™
  • Shield 1: Copper/Polyester Tape
  • Drain Wire: 16 AWG Stranded Bare Copper
  • Shield 2: Copper/Polyester Tape
  • Belt: Black Fire-Roc™ Binder
  • Armor: CCW Copper
  • Optional Jacket: Non-Halogen Flame Retardant Polyolefin

Applications:

Low voltage critical circuits where increased physical protection is required.

  • Transit tunnels & platforms
  • Underground & below grade structures
  • Petrochemical, nuclear, and waste treatment facilities

36516, 36517, 36518, 36519, 36520, 36521, 36522, 36523

Part Numbers & Specs

SpecPart NumberNumber of ConductorsNominal Core Diameter (in/mm)Nominal Armor Diameter (in/mm)Nominal Cable Diameter over Outer Jacket (in/mm)Approximate Net Weight (Lbs/1000 ft.)
14 AWG Armored - No Overall Jacket
Spec3651620.334/8.4840.620/15.748N/A264
Spec3672730.377/9.5760.700/17.780N/A368
Spec3651740.504/12.8020.840/21.336N/A447
Spec3672850.463/11.7600.780/19.812N/A435
Spec3651860.538/13.6650.880/22.352N/A506
Spec3672970.506/12.8520.820/20.828N/A481
Spec3651980.605/15.3670.920/23.368N/A589
14 AWG Armored - With Overall Jacket
Spec3652020.334/8.4840.620/15.7480.684/17.374306
Spec3673030.377/9.5760.700/17.7800.795/20.193440
Spec3652140.504/12.8020.840/21.3360.934/23.724532
Spec3673150.463/11.7600.780/19.8120.874/22.200515
Spec3652260.538/13.6650.880/22.3520.974/24.740601
Spec3673270.506/12.8520.820/20.8280.914/23.216565
Spec3652380.605/15.3670.920/23.3681.024/26.100682
16 AWG Shielded & Armored - No Overall Jacket
Spec3673520.370/9.3980.660/16.764N/A297
Spec3673630.372/9.4490.660/16.764N/A328
Spec3673740.740/18.7961.043/26.492N/A480
Spec3673850.450/11.4300.780/19.812N/A357
Spec3673960.799/20.2951.155/29.337N/A581
Spec3674070.471/11.9630.840/21.336N/A478
Spec3674180.860/21.8441.220/30.988N/A664
16 AWG Shielded & Armored - With Overall Jacket
Spec3674220.370/9.3980.660/16.7640.724/18.390346
Spec3674330.372/9.4490.660/16.7640.724/18.390373
Spec3674440.740/18.7961.043/26.4921.167/29.642620
Spec3674550.450/11.4300.780/19.8120.844/21.438470
Spec3674660.799/20.2951.155/29.3371.279/32.487736
Spec3674770.471/11.9630.840/21.3360.934/23.724563
Spec3674880.860/21.8441.220/30.9881.344/34.14826

Notes:

  • Refer to installation instructions for hardware certifications
  • Refer to R27557 Fire Resistive Cable (UL)
  • VITALink® Brand Type FPLR-ST1, CL3R-ST1, CSA FAS105 ST1 FT4 for use in System No. FHIT.40B and FHIT7.40B
  • Authorities having Jurisdiction should be consulted before installation

Compliance:

  • UL Listed Type FPLR-ST1
  • UL Listed CL3R-ST1
  • CSA Listed FAS 105 ST1 FT4
  • UL Subject 1424 for Power Limited Fire Alarm Circuits; 300V/105°C Classified
  • UL Subject 13 for Power Limited Circuit Cables; 300V/105°C Classified
  • ANSI/UL 2196 2 Hour Fire Rating for use in FHIT System 40B
  • CAN/ULC-S139 2 Hour Fire Rating with Hose Stream fro use in FHIT7 System 40B
  • NFPA 70 & 72
  • California State Fire Marshal
  • RoHS Compliant